Part III: Culture
laboratory layout and equipment

Plan of a culture laboratory
Persons who work with tubercle bacilli are at risk of laboratory-acquired infection, mainly by the airborne route, and it is well-known that sensible laboratory design may contribute much to the prevention of such infections. The detailed arrangement of a tuberculosis laboratory will vary according to the size and shape of the available room, the type of laboratory activity and whether other work is also done in the same room. Nevertheless, the most important aspect in tuberculosis laboratory design is to ensure a logical flow of specimens and activities, from clean to less clean areas.

Mycobacterial cultures should always be performed in containment laboratories, physically separated from other laboratory areas. The objective is to reduce the infection risk, not only to tuberculosis technologists, but also to other individuals in the same building.

Contrary to common belief containment laboratories need not be overly sophisticated and expensive. Sophisticated and expensive air conditioning is not an essential requirement in tuberculosis culture laboratories. Rather, the principle should be that, during working hours, air is continuously extracted to the outside of the laboratory either through a biological safety cabinet or through simple extraction fans in walls or windows. Ventilation standards for air changes and pressure gradients should be considered in relation to the number of specimens processed per year and the prevalence of tuberculosis among these specimens. If bacteriological methods are performed with strict adherence to safety standards and high risk procedures are limited to the bio-safety cabinet, air-borne contamination will be minimised. Six to twelve room air changes per hour are sufficient to remove up to 99% of airborne particles within 30 to 45 minutes.

Supply and exhaust air devices should be located on opposite side walls, with supply air provided from clean areas and exhaust air taken from less clean areas. An excess of air supply of 50 cubic feet per minute (23.6 litres per second) or a similar negative pressure created by extracting air is sufficient to obtain the necessary pressure gradient. Air should be exhausted directly to the outside. Potentially contaminated air should be discharged at least 3m above ground level.

Figure 1 illustrates a floor plan for a tuberculosis culture laboratory with air flow in one direction, from clean to less clean areas.

Arranging equipment and materials
Entry to the laboratory is via the officewhich contains the facilities necessary for administration and management of the laboratory. These include storage space for laboratory registers, laboratory reports, chemicals and reagents.

Specimens arriving at the laboratory are presented through a window/hatch to a separate reception counter. Here, specimen containers are checked for leakage and their surfaces decontaminated. Cross-checking of laboratory request forms against specimens is also done and the relevant details are entered into the laboratory register. On completion of these activities the specimens are passed into the main laboratoryarea for further processing.

The main laboratory area contains all the facilities necessary for smear preparation, for specimen decontamination and digestion, and for inoculation of media and incubation of cultures. This area houses work benches, a pH meter, a large domestic refrigerator, a wash basin with elbow-controlled taps and storage cabinets. The isolation area is situated at the most extreme end of the main laboratory and contains a biological safety cabinet and a centrifuge.

The reading room is reserved for performing microscopy on smears prepared in the main laboratory and for reading of cultures. This area contains work benches, a microscope and an elbow-operated wash basin. Laboratory reports may be completed here and then passed to the office for dissemination and entering of data into the laboratory register.

The kitchen functions as an area for the disposal of cultures and for subsequent cleaning and sterilisation of glassware. This area houses work benches, a large double-wash stainless steel sink and an autoclave.

In many countries, media preparation is performed at the central level only. If, however, media is prepared as part of the activities of the culture laboratory, a separate media preparation area is recommended. This area houses workbenches, an inspissator, a domestic refrigerator and a wash-basin with elbow-operated taps.

Before the processing of specimens and the preparation of cultures are started, equipment and materials should be arranged to ensure a logical and safe flow of work. All manipulations should be standardised and the arrangement of materials should always be the same to ensure maximum safety, as illustrated by Figure 2. For left-handed technologists it may be more convenient to arrange all or most items in the opposite direction, ie. in a mirror-image.

Care and maintenance of essential equipment
Annex 1 contains a list of essential equipment and supplies for a culture laboratory using egg-based Löwenstein-Jensen culture medium, and 4% sodium hydroxide for specimen decontamination. Before purchasing new equipment and supplies it is worthwhile to obtain personal advice of laboratory persons who have had experience in their use. Do not rely entirely on advertisements, catalogues, extravagant claims of sales representatives and the opinion of purchasing officers.

Biological safety cabinet
Selecting the right model
The single most important piece of laboratory equipment needed in a tuberculosis culture laboratory is a well-maintained, properly functioning biological safety cabinet (BSC). These cabinets have been designed to provide a combination of staff, environmental or product protection when appropriate practices and procedures are followed. BSCs use high efficiency particulate air (HEPA) filters in their exhaust and/or air supply systems. HEPA filters remove particles equal to and greater than 0.3Fm (which essentially includes all bacteria, spores and viruses) with an efficiency of 99.97%.

Microbiological risks are assigned to biosafety levels I through IV.Mycobacterium tuberculosis is classified under Risk Group III. This group includes microorganisms that are particularly associated with infection by the airborne route. Precautions therefore involve measures to minimise the production and dispersal of aerosols and infected airborne particles and to prevent the laboratory worker from inhaling those that might be released, as well as measures intended to prevent infection by accidental ingestion and inoculation.

Of the three classes of biological safety cabinets, Class I and Class II are suitable for tuberculosis bacteriology. The Class I BSC provides staff and environmental protection, but no product protection (Figure 3).

Unfiltered room air is drawn across the work surface. Staff protection is provided by this inward air flow as long as a minimum velocity of 75 linear feet per minute (22.8 meter per second) is maintained through the front opening. Any airborne bacteria are entrained and conveyed into the HEPA filter. The Class I BSC is hard-ducted to the building exhaust system and the building exhaust fan provides the negative pressure necessary to draw room air into the cabinet. Modern cabinets have airflow indicators and warning devices. The filters must be changed when the airflow falls below the minimum velocity level.

Class II BSCs provide staff, environmental and product protection. Air flow is drawn around the operator into the front grille of the cabinet, which provides staff protection. In addition, the downward laminar flow of HEPA-filtered air provides product protection by minimising the chance of cross-contamination along the work surface of the cabinet (Figure 4). Because cabinet air has passed through the exhaust HEPA filter, it is contaminant-free and may be circulated back into the laboratory (Type A BSC) or ducted out of the building (Type B BSC).

If a Class II BSC is preferred for tuberculosis bacteriology, the ?thimble system? should be used in stead of an extract fan, as indicated by Figure 5. The thimble allows air to be extracted continuously from the room and from the safety cabinet when it is in use.

Placement of the BSC
The ideal location for the BSC is remote from the entry to the laboratory (eg. the rear of the laboratory away from traffic) since people walking parallel to the BSC can disrupt the air curtain. This curtain is quite fragile, amounting to a nominal inward and downward velocity of 1 mile per hour (1.609 kilometer per hour). Open windows or laboratory equipment that create air movement (eg. centrifuges) should not be located near the BSC.

Centrifuge
Centrifuges are essential in laboratories where tubercle bacilli are cultured. Methods involving the use of a centrifuge are more efficient than simple decontamination and culture of sputum directly onto medium.

The recommended centrifuge for use in tuberculosis culture laboratories is a floor model with a lid and fixed angle rotor which contains sealed centrifuge buckets. Because of its great mass in relation to that of the centrifuge tubes, the fixed angle rotor permits centrifugation of tubes with small weight differences without causing vibration and possible tube breakage. For maximum safety, sealed centrifuge buckets should be fitted. These are usually made of stainless steel and are fitted with rubber buffers. They are paired and their weight engraved on them. Sealed buckets are always used in pairs, opposite one another and it is convenient to paint each pair with different colour patches to facilitate recognition. If the buckets fit in the centrifuge head on trunnions, these are also paired.

Centrifuges should preferably be fitted with an electrically operated safety catch which prevents the lid from being opened while the rotor is spinning.

Many reports and manuals describing sputum processing in tuberculosis laboratories record centrifuge speeds in revolutions per minute (rpm). However, revolutions per minute is a measure of speed for a particular centrifuge head and not a measure of sedimenting efficiency or relative centrifugal force (RCF). The amount of artificial gravity created by the spinning of a centrifuge is determined by the rate of spin (revolutions per minute) and by the distance from the centre of the spinning head to an outer point where the force is to be measured. This relative centrifugal force can be increased by either increasing the rate of spin or the distance from the centre and is expressed in multiples of g, eg. 3000 x g. The RCF may be calculated from the following formula:

RCF = 1.12Rmax (rpm/1000)2
where Rmax = radius (mm) from the center of the rotating head to the bottom of the spinning centrifuge tube
The required rpm to generate a desired RCF may be calculated as follows:
rpm = 1000

If the RCF is not high enough, many mycobacteria will remain in suspension following centrifugation and will be poured off with the discarded supernatant. A 95% sedimenting efficiency should be attained for optimal isolation of mycobacteria. This requires a RCF of 3 000 x g. Many of the old centrifuges still used in tuberculosis laboratories commonly spin at 2 300 to 3 000 rpm (only 1 500-2 000 RCF); most users of such equipment spin digested specimens for 15 minutes, thereby achieving sedimenting efficiencies ranging from 75%-84% and lower.

Depending on the type of rotor in a non-refrigerated centrifuge and the number of runs, the temperature in the specimen tube may increase by 4EC to 18EC. Tubes spun in a streamlined angle head are least affected by temperature rise even after several runs, but the contents of tubes in unprotected horizontal rotors may exceed 40EC if the centrifuge has been used for five or more successive runs. Even when centrifuge time remains consistent at 15 minutes, the percentage of organisms killed increase from 13% to 22% to 30% as the temperature rises from 20EC to 30EC to 40EC. It is, therefore, important to keep the spinning time low (15 minutes) and the RCF high (3 000 x g) to achieve 95% sedimentation. The use of angle head rotors minimises heat build-up due to air friction.

Glass tubes may break under the stress of centrifugation. If a centrifuge tube breaks, the liquid will splash or be blown out and aerosolised. Screw top centrifuge tubes should therefore be used for potentially infectious material.

The centrifuge head must be in balance while spinning. An out-of-balance head vibrates and may break. If a tube is added to one side of the head, an equivalent weight must be added to the opposite side. Tubes used in processing specimens will usually be balanced if matched pairs have matched levels of liquid in them. As an added safety precaution, matched tubes should contain 70% ethanol rather than water, which may limit the risk of infection should breakage occur.

Do not touch any centrifuge head while it is spinning. Touching it may not only cause injury, it may also cause rapid or erratic stops which stir and resuspend the sediment. Some centrifuges are equipped with a brake to gradually slow the spinning head.

35E-37EC incubator
Cultures are incubated at 35E-37EC for eight weeks. Incubators are available in various sizes. In general, it is best to obtain the largest possible model that can be accommodated and afforded. Small incubators suffer wide fluctuations in temperature when the doors are opened. Ensure a proper circulation of air by avoiding overloading and by using perforated trays. Maintain a constant temperature by not opening the incubator door unnecessarily.

Although incubators rarely develop faults, it is advisable, before choosing one, to ascertain that service facilities are available. The electrical circuits are not complex but require expert technical knowledge to repair. Transporting incubators back to the manufacturers is most inconvenient.

In a laboratory with a large volume of cultures it is of great advantage to incubate them in an incubator room. A hot room or walk-in incubator is not difficult to adapt from a small room or corner of a large room: Windows must be blocked up. The walls need two layers of building paper on which is glued 48mm-thick slabs of expanded polystyrene or cork (more expensive) between battens at 600mm centres. The inner lining can be ordinary plaster or insulation board. The ceiling must be lagged in the same way and in rooms lower false ceilings are preferable. The floor can be covered with insulation board and hardboard and the doors lagged in their inner surfaces in the same way, and fitted in their jambs on sponge rubber draught-prevention strips.

Two methods of heating are possible. Tubular heaters around the walls are satisfactory and a power of 3kW is more than adequate for a room of 5-7m3 to be maintained at 37EC. A large circulating fan to avoid hot and cold spots must be fitted on one wall and should operate constantly. An alternative arrangement is the greenhouse-or space-heater in which a 2.5-3.0 kW heater and a fan are built into a steel casing. The wiring must be altered so that the fan is always on and the heater connected to sensitive thermostats. (The thermostats build into ordinary greenhouse- or space heaters are too coarse for this purpose). Two thermostats are recommended, one normally operational at 37EC and the other set to turn off heating at around 39EC as a precaution against failure of the first thermostat and consequent over-heating of cultures. The two methods of heating may be combined. Smaller tubular heaters, permanently switched on, will supply background heat and the space heater will maintain the required temperature.

Wooden shelving and racks are undesirable. If a high humidity is maintained fungi may grow on the wood. Steel or aluminium racks are preferable and can be custom-made. Shelves should be free, ie. removed easily for cleaning and there should be space between the shelves and the walls to allow for circulation of air.

Inspissator
In the preparation of slopes of egg-based medium the amount of heating required to coagulate the protein must be carefully controlled. A steamer heats the medium too rapidly and raises the temperature too high.

Inspissators for the preparation of egg-based culture medium should be able to reach and maintain a constant temperature of 80E-85EC for 45 minutes. Modern inspissators are thermostatically controlled and fitted with a large internal circulating fan. Inside shelves on which the tubes are sloped should be made of wire mesh so that circulation is not impeded. It is convenient to have wire mesh or aluminium racks made which hold tubes or bottles at the correct angle (5E-10E) and which slide onto the shelf brackets. These facilitate rapid loading and unloading while the inspissator is hot.

A glass door that seals off the inside of the oven will contribute to maintaining the required temperature and is recommended.It is also recommended that the required temperature be raised first before batches of media are loaded for inspissation.

Autoclave
Tubercle bacilli are more readily killed by moist heat (saturated steam) than by dry heat. Steam kills tubercle bacilli by denaturing their protein. Air has an important influence on the efficiency of steam sterilisation because its presence changes the pressure-temperature relationship. For example, the temperature of saturated steam at 15 lb/in2 is 121EC, provided that all of the air is first removed from the vessel. With only half of the air removed the temperature of the resulting air-steam mixture at the same pressure is only 112EC. In addition, the presence of air in mixed loads will prevent penetration by steam.

All of the air that surrounds and permeates the load must first be removed before steam sterilisation can commence. Materials to be sterilised should therefore be packed loosely. Contaminated material (eg. discarded cultures) should be in solid bottomed containers not more than 20cm deep. Large air spaces should be left around each container and none should be covered.

Only autoclaves designed for laboratory work and capable of dealing with a mixed load should be used. ?Porous load? and ?bottled fluid sterilisers? are not satisfactory for laboratory work. Two varieties of laboratory autoclaves are suitable:

  • pressure cooker types
  • gravity displacement models with automatic air and condensable discharge

Pressure cooker autoclaves
The most common type is a device for boiling water under pressure. It has a vertical metal chamber with a strong metal lid which can be fastened down and sealed with a rubber gasket. An air and steam discharge tap, pressure gauge and safety valve are fitted in the lid. Water in the bottom of the autoclave is heated by external gas burners, an electric immersion heater or a steam coil.

Figure 6 illustrates a typical pressure cooker autoclave.

Autoclaves with air discharge by gravity displacement
These autoclaves are usually arranged horizontally and are rectangular in shape, thus making the chamber more convenient for loading. A palette and trolley system can be used. Figure 7 shows in diagrammatic form a jacketed gravity displacement type of autoclave. Similar autoclaves can be constructed without jackets. The door should have a safety device to ensure that it cannot be opened while the chamber is under pressure.

The jacket surrounding the autoclave consists of an outer wall enclosing a narrow space around the chamber, which is filled with steam under pressure to keep the chamber wall warm. The steam enters the jacket from the mains supply, which is at high pressure, through a valve that reduces this pressure to the working level. The working pressure is measured on a separate pressure gauge fitted to the jacket. This jacket also has a separate drain for air and condensate to pass through.

The steam enters the chamber from the same source which supplies steam to the jacket. It is introduced in such a way that it is deflected upwards and fills the chamber from the top downwards, thus forcing the air and condensate to flow out of the drain at the base of the chamber by gravity displacement. The drain is fitted with strainers to prevent blockage by debris. The drain is usually fitted with a thermometer for registering the temperature of the issuing steam. The temperature recorded by the drain thermometer is often lower than that in the chamber. A ?near-to-steam? trap is also fitted.

The automatic steam trap or 'near-to-steam' trap is designed to ensure that only saturated steam is retained inside the chamber, and that air and condensate, which are at a lower temperature than saturated steam, are automatically discharged. It is called a 'near-to-steam' trap because it opens if the temperature fall to about 2EC below that of saturated steam and closes within 2EC to the saturated steam temperature.

The trap operates by the expansion and contraction of a metal bellows, which opens and closes a valve. The drain discharges into a tundish in such a way that there is a complete airbreak between the drain and the dish. This ensures that no contaminated water can flow back from the waste-pipe into the chamber.

Water bath
The contents of a test tube placed in a water bath are raised to the required temperature much more rapidly than in an incubator. Water baths are therefore useful for short term incubation required, for example, in some biochemical tests.

Modern water baths are equipped with electrical stirrers and in some the heater, thermometer and stirrer are in one unit, easily detached from the batch for servicing. Water baths must also be lagged so as to prevent heat loss through the walls. A bath that has not been lagged by the manufacturers can be insulated with slabs of expanded polystyrene.

Water baths should be fitted with lids in order to prevent heat loss and evaporation. These lids must slope so that condensation water does not drip on the contents. To avoid chalky deposits on tubes and internal surfaces only distilled water should be used.

Bunsen burners
For material that may spatter or that is highly infectious a hooded Bunsen burner should be used. Electric burners are also available. These are tubular micro-incinerators in which the loop or wire is inserted, and is recommended for use in BSCs.

Glassware and plastics
Soda-glass or pyrex are satisfactory for tuberculosis culture and the use of more expensive resistance glass is not justified. New unwashed soda-glass should be soaked in hydrochloric acid overnight to partially neutralise the alkali content of the glass.

Culture bottles
Several sizes of culture bottles are useful for tuberculosis bacteriology. The most useful sizes are the small McCartney (14ml), the standard McCartney (28ml) and the Universal container (28ml), which has a larger neck than the others and is also used as a specimen container. These bottles usually have aluminium screw caps with rubber liners. The liners should be made of black rubber; some red rubbers are thought to give off bactericidal substances.

Test tubes
Rimless test tubes of heavy quality are most suitable for tuberculosis bacteriology. Thin glass, lipped chemical tubes should not be used. The most frequently used sizes of test tubes are 152x16mm, holding 5-10ml and 152x19mm, holding 10-15ml.

Cotton wool plugs have been used for many years to stopper test tubes but have largely been replaced by metal caps. Aluminium caps (Cap-O-Test) closures are recommended. They have a wide tolerance and fit most tubes, being held in place with a small spring. These caps are inexpensive, last a long time, are available in many colours and save a great deal of time and labour.

Temporary closures for bottles, flasks and tubes can be made from kitchen aluminium foil.

Pasteur pipettes
Pasteur pipettes are probably the most dangerous pieces of laboratory equipment in unskilled hands. Safer pasteur pipettes with integral teats and made of low density polypropylene (rather than glass) are available and are supplied pre-sterilised.

Pasteur pipettes are used once only.

Graduated pipettes
Straight side blow out pipettes, 1-10ml capacity are often used. They must be plugged with non-absorbent cotton wool at the suction end to prevent bacteria from entering from the teat and contaminating the material in the pipette. These plugs must be tight enough to stay in place during pipetting but not so tight that they cannot be removed during cleaning. About 25mm of non-absorbent cotton wool is pushed into the end with a piece of wire. The ends are then passed through a Bunsen flame to tidy them. (Wisps of cotton wool which get between the glass and the teat may permit air to enter and the contents to leak).

Rubber teats
Rubber teats provide a safe alternative to the highly dangerous practice of mouth pipetting. Teats with a capacity greater than that of the pipettes for which they are intended should be used, eg. a 1ml teat for pasteur pipettes, a 2ml teat for a 1ml pipette etc. (otherwise the teat must be fully compressed, which is tiring). Most novice laboratory workers compress the teat completely, then suck up the liquid and try to hold it at the mark while transferring it. This is unsatisfactory and leads to spilling and inaccuracy. Compress the teat just enough to suck the liquid a little way pass the mark of the pipette. Withdraw the pipette from the liquid, press the teat lightly to bring the fluid to the mark and then release it. The correct volume is now held in the pipette without tiring the thumb and without risking loss. To discharge the pipette, press the teat slowly and gently and then release it in the same way. Violent operation usually fails to eject all the liquid; bubbles are sucked back and aerosols are formed.

Inoculating loops and wires
These are usually made of 25 SWG Nicrome wire. They should be short (not more than 15cm long) in order to minimise vibration and therefore involuntary discharge of contents. Loops should be small (not more than 5mm in diameter). Large loops are inclined to empty spontaneously and scatter infected airborne particles. Loops should be completely closed. This can be achieved by twisting the end of the wire round the shank, or by taking a piece of wire 15cm long, bending the centre round a nail or rod of appropriate diameter and twisting the ends together in a drill chuck.

Loops and wires should not be fused into glass rods. Aluminium holders are available from most laboratory suppliers.

Disposable loops are excellent, albeit more expensive.

Racks and baskets
Test tube and culture bottle racks should preferably be made of polypropylene or nylon so that they can be autoclaved. This also minimises breakage, which is not uncommon when metal racks are used. Wooden racks are unhygienic.

Traditional wire baskets are unsafe for holding test tubes. They contribute to breakage hazards and do not retain spilled fluids. Autoclavable plastic boxes of various sizes are safer for use with cultures.

CONTACTS:

Dr Karin Weyer
E-mail: karin.weyer@mrc.ac.za
Dr Roxanna Rustomjee
E-mail: roxanna.rustomjee@
mrc.ac.za

Prof Valerie Mizrahi
E-mail: mizrahiv@
pathology.wits.ac.za

Prof. Paul van Helden
E-mail: pvh@sun.ac.za

 

Last updated:
10-Feb-2006

Technical enquiries:
Webmaster

Copyright © 1999-current
SAHealthInfo TM

To SAHealthInfo home